FS17 450/750V
FS17 can be installed in concealed or exposed pipes or conduits.
Suitable for fixed protection type of mounting, for use on or in lighting or control equipment, for use with voltages up to and including 1000 AC or 750 DC.
application
FS17 – 450/750V cables are intended for general application sites in construction projects with requirements for fire performance; suitable for applications with a high risk of fire in a bundle installation, with a fire performance grade of Cca – s3, d1, a3.
For more information and guidance, please refer to CEI EN 50565 – 1 and CEI EN 50565 – 2 standards.
Function
- – CEI-UNEL 35716;
- – CEI EN/IEC 60228;
- – CEI EN/IEC 60332-1-2;
- – CEI EN 50267-2-1;
- – CPR EN 50399
- – CEI EN 50525-1 p.q.a./a.p.;
- – CEI EN 50525-2-31 p.q.a./ a.p.;
- – CEI EN 60754-2; EN 61034-2;
- – EN 50575:2014+A1:2016;
- – CEI 64-8:V4.
Additional information
- Customizable color
- Customizable to adapt to higher temperatures
Product structure
Conductor | Soft non-plated annealed twisted copper wire, fifth conductor. (CEI EN/IEC 60228 standard) |
---|---|
Insulation | S17 type low halogen polyvinyl chloride for low corrosive gas emission |
Insulation color | Blue, dark blue, light blue, black, brown, gray, yellow/green, red, white, cyan, purple, orange, pink |
Technical parameters
Working voltage | Uo/U 450 / 750V |
---|---|
Test voltage | 2500 volts |
Bending radius | ≥ 10 square millimeters, 4 *D
Other cases are 4 – 6 *D |
Temperature range | Fixed laying: -15/+90°C
Flexible application: -5/+70°C Short-circuit maximum temperature; 250°C |
Tensile strength | 1.5 kilograms/square millimeter |
No halogen | CEI EN 50565 – 1, EN 50565-2 |
Fire resistance | Flame retardant and self-extinguishing, in accordance with IEC 60332-1-2 + VDE 0482-332-1-2 standard |
Oil resistance | Understand internal standards |
Executive Standard | 2014/35/UE (B.T.) – 2011/65/CE ; 2015/863/UE(RoHS); 305/2011 EU |
Environmental protection | Complies withEURoHS directive |
Cable parameters
Number | Specifications | Insulation thickness | Outer diameter – ø | Cable weight ≈ | Maximum resistance (20°C) | |
---|---|---|---|---|---|---|
L02620207 | 1 square millimeter | 0.7 mm | 3,0 mm | 15 kilograms/kilometer | 19.5 ohms/kilometer | Send inquiry |
L02620307 | 1.5 square millimeters | 0.7 mm | 3.4 mm | 21 kilograms/kilometer | 13.3 Ohm/km | Send inquiry |
L02620407 | 2.5 mm² | 0.8 mm | 4,1 mm | 32 kilograms/kilometer | 7.98 ohms/km | Send inquiry |
L02620507 | 4 square millimeters | 0.8 mm | 4.8 mm | 47 kilograms/kilometer | 4.95 ohms/km | Send inquiry |
L02620707 | 6 square millimeters | 0.8 mm | 5,3 mm | 65 kilograms/kilometer | 3.30 Ohm/km | Send inquiry |
L02621207 | 10 square millimeters | 1,0 millimeters | 6,8 mm | 110 kilograms/kilometer | 19.1 Ohm/km | Send inquiry |
L02621807 | 16 square millimeters | 1,0 millimeters | 8,1 mm | 170 kilograms/kilometer | 1.21 Ohm/km | Send inquiry |
L02622007 | 25 square millimeters | 1,2 mm | 10,2 mm | 255 kilograms/kilometer | 0.78 Ohm/km | Send inquiry |
L02622507 | 35 square millimeters | 1,2 mm | 11.7 mm | 345 kilograms/kilometer | 0.554 ohm/kilometer | Send inquiry |
L02620210 | 50 square millimeters | 1,4 mm | 13,9 mm | 495 kilograms/kilometer | 0.386 ohm/km | Send inquiry |
L02620310 | 70 mm² | 1,4 mm | 16,0 mm | 680 kilograms/kilometer | 0.272 ohms/kilometer | Send inquiry |
L02620410 | 95 square millimeters | 1.6 mm | 18,2 mm | 900 kilograms/kilometer | 0.206 ohm/km | Send inquiry |
L02620510 | 120 mm² | 1.6 mm | 20,2 mm | 1135 kilograms/kilometer | 0.161 Ohm/km | Send inquiry |
L02620710 | 150 mm² | 1.8mm | 22.5 mm | 1412 kilograms/kilometer | 0.128 Ohm/km | Send inquiry |
L02621210 | 185 mm² | 2.0 mm | 24,9 mm | 1920 kilograms/kilometer | 0.106 ohm/km | Send inquiry |
L02621810 | 240 mm² | 2,2 mm | 28,4 mm | 2260 kilograms/kilometer | 0.0801 ohm/km | Send inquiry |