FS17 450/750V

FS17 can be installed in concealed or exposed pipes or conduits.

Suitable for fixed protection type of mounting, for use on or in lighting or control equipment, for use with voltages up to and including 1000 AC or 750 DC.

application

FS17 – 450/750V cables are intended for general application sites in construction projects with requirements for fire performance; suitable for applications with a high risk of fire in a bundle installation, with a fire performance grade of Cca – s3, d1, a3.

For more information and guidance, please refer to CEI EN 50565 – 1 and CEI EN 50565 – 2 standards.

Function

  • – CEI-UNEL 35716;
  • – CEI EN/IEC 60228;
  • – CEI EN/IEC 60332-1-2; 
  • – CEI EN 50267-2-1;
  • – CPR EN 50399
  • – CEI EN 50525-1 p.q.a./a.p.; 
  • – CEI EN 50525-2-31 p.q.a./ a.p.;
  • – CEI EN 60754-2; EN 61034-2;
  • – EN 50575:2014+A1:2016;
  • – CEI 64-8:V4.

Additional information

  • Customizable color
  • Customizable to adapt to higher temperatures

Product structure

Conductor Soft non-plated annealed twisted copper wire, fifth conductor. (CEI EN/IEC 60228 standard)
Insulation S17 type low halogen polyvinyl chloride for low corrosive gas emission
Insulation color Blue, dark blue, light blue, black, brown, gray, yellow/green, red, white, cyan, purple, orange, pink

Technical parameters

Working voltage Uo/U 450 / 750V
Test voltage 2500 volts
Bending radius ≥ 10 square millimeters, 4 *D

Other cases are 4 – 6 *D

Temperature range Fixed laying: -15/+90°C

Flexible application: -5/+70°C

Short-circuit maximum temperature; 250°C

Tensile strength 1.5 kilograms/square millimeter
No halogen CEI EN 50565 – 1, EN 50565-2
Fire resistance Flame retardant and self-extinguishing, in accordance with IEC 60332-1-2 + VDE 0482-332-1-2 standard
Oil resistance Understand internal standards
Executive Standard 2014/35/UE (B.T.) – 2011/65/CE ; 2015/863/UE(RoHS); 305/2011 EU
Environmental protection Complies withEURoHS directive

 

Cable parameters

Number Specifications Insulation thickness Outer diameter – ø Cable weight ≈ Maximum resistance (20°C)
L02620207 1 square millimeter 0.7 mm 3,0 mm 15 kilograms/kilometer 19.5 ohms/kilometer Send inquiry
L02620307 1.5 square millimeters 0.7 mm 3.4 mm 21 kilograms/kilometer 13.3 Ohm/km Send inquiry
L02620407 2.5 mm² 0.8 mm 4,1 mm 32 kilograms/kilometer 7.98 ohms/km Send inquiry
L02620507 4 square millimeters 0.8 mm 4.8 mm 47 kilograms/kilometer 4.95 ohms/km Send inquiry
L02620707 6 square millimeters 0.8 mm 5,3 mm 65 kilograms/kilometer 3.30 Ohm/km Send inquiry
L02621207 10 square millimeters 1,0 millimeters 6,8 mm 110 kilograms/kilometer 19.1 Ohm/km Send inquiry
L02621807 16 square millimeters 1,0 millimeters 8,1 mm 170 kilograms/kilometer 1.21 Ohm/km Send inquiry
L02622007 25 square millimeters 1,2 mm 10,2 mm 255 kilograms/kilometer 0.78 Ohm/km Send inquiry
L02622507 35 square millimeters 1,2 mm 11.7 mm 345 kilograms/kilometer 0.554 ohm/kilometer Send inquiry
L02620210 50 square millimeters 1,4 mm 13,9 mm 495 kilograms/kilometer 0.386 ohm/km Send inquiry
L02620310 70 mm² 1,4 mm 16,0 mm 680 kilograms/kilometer 0.272 ohms/kilometer Send inquiry
L02620410 95 square millimeters 1.6 mm 18,2 mm 900 kilograms/kilometer 0.206 ohm/km Send inquiry
L02620510 120 mm² 1.6 mm 20,2 mm 1135 kilograms/kilometer 0.161 Ohm/km Send inquiry
L02620710 150 mm² 1.8mm 22.5 mm 1412 kilograms/kilometer 0.128 Ohm/km Send inquiry
L02621210 185 mm² 2.0 mm 24,9 mm 1920 kilograms/kilometer 0.106 ohm/km Send inquiry
L02621810 240 mm² 2,2 mm 28,4 mm 2260 kilograms/kilometer 0.0801 ohm/km Send inquiry

Other sizes and colors can be customized.The above data is for reference only, subject to the actual product.