H07V2-U 450/750 V
FS17 can be installed in concealed or exposed pipes or conduits.
Suitable for fixed protection type of mounting, for use on or in lighting or control equipment, for use with voltages up to and including 1000 AC or 750 DC.
application
These cables are used for fixed installation in electrical equipment or inside or outside lighting fixtures under the premise of protection. Only in signal and control circuits, suitable for surface mounting or embedded conduit. The conductor can reach a maximum temperature of 90°C under normal use. No further contact with other objects above 85°C.
HD 21.7 S2, VDE-0281 Part 7, CEI20-20/7, CE Low Voltage Directive 73/23/EEC and 93/68/EEC, ROHS Certified.
Function
- – CEI-UNEL 35716;
- – CEI EN/IEC 60228;
- – CEI EN/IEC 60332-1-2;
- – CEI EN 50267-2-1;
- – CPR EN 50399
- – CEI EN 50525-1 p.q.a./a.p.;
- – CEI EN 50525-2-31 p.q.a./ a.p.;
- – CEI EN 60754-2; EN 61034-2;
- – EN 50575:2014+A1:2016;
- – CEI 64-8:V4.
Additional information
- Customizable color
- Customizable to adapt to higher temperatures
Product structure
Conductor | Solid bare copper single-strand conductor Single core, in accordance with DIN VDE 0281-3, HD 21.3 S3 and IEC 60227-3 |
---|---|
Insulation | PVC TI3 insulation |
Insulation color | The color coding of the wire core follows VDE-0293- H07V-U (16 gauge and above) |
Technical parameters
Working voltage | Uo/U 450 / 750V |
---|---|
Test voltage | 2500 volts |
Bending radius | Dynamic bend radius: 15 x Ø
Static bend radius: 15 x Ø |
Temperature range | Fixed laying: -30/+80°C
Flexible application: -5/+70°C Short-circuit maximum temperature; 160°C |
Tensile strength | 1.5 kilograms/square millimeter |
No halogen | CEI EN 50565 – 1, EN 50565-2 |
Fire resistance | Flame retardant in accordance with IEC 60332.1 |
Oil resistance | Understand internal standards |
Executive Standard | 2014/35/UE (B.T.) – 2011/65/CE ; 2015/863/UE(RoHS); 305/2011 EU |
Environmental protection | Complies withEURoHS directive |
Cable parameters
Number | Specifications | Insulation thickness | Outer diameter – ø | Cable weight ≈ | Maximum resistance (20°C) | |
---|---|---|---|---|---|---|
L02620207 | 1 square millimeter | 0.7 mm | 3,0 mm | 15 kilograms/kilometer | 19.5 ohms/kilometer | Send inquiry |
L02620307 | 1.5 square millimeters | 0.7 mm | 3.4 mm | 21 kilograms/kilometer | 13.3 Ohm/km | Send inquiry |
L02620407 | 2.5 mm² | 0.8 mm | 4,1 mm | 32 kilograms/kilometer | 7.98 ohms/km | Send inquiry |
L02620507 | 4 square millimeters | 0.8 mm | 4.8 mm | 47 kilograms/kilometer | 4.95 ohms/km | Send inquiry |
L02620707 | 6 square millimeters | 0.8 mm | 5,3 mm | 65 kilograms/kilometer | 3.30 Ohm/km | Send inquiry |
L02621207 | 10 square millimeters | 1,0 millimeters | 6,8 mm | 110 kilograms/kilometer | 19.1 Ohm/km | Send inquiry |
L02621807 | 16 square millimeters | 1,0 millimeters | 8,1 mm | 170 kilograms/kilometer | 1.21 Ohm/km | Send inquiry |
L02622007 | 25 square millimeters | 1,2 mm | 10,2 mm | 255 kilograms/kilometer | 0.78 Ohm/km | Send inquiry |
L02622507 | 35 square millimeters | 1,2 mm | 11.7 mm | 345 kilograms/kilometer | 0.554 ohm/kilometer | Send inquiry |
L02620210 | 50 square millimeters | 1,4 mm | 13,9 mm | 495 kilograms/kilometer | 0.386 ohm/km | Send inquiry |
L02620310 | 70 mm² | 1,4 mm | 16,0 mm | 680 kilograms/kilometer | 0.272 ohms/kilometer | Send inquiry |
L02620410 | 95 square millimeters | 1.6 mm | 18,2 mm | 900 kilograms/kilometer | 0.206 ohm/km | Send inquiry |
L02620510 | 120 mm² | 1.6 mm | 20,2 mm | 1135 kilograms/kilometer | 0.161 Ohm/km | Send inquiry |
L02620710 | 150 mm² | 1.8mm | 22.5 mm | 1412 kilograms/kilometer | 0.128 Ohm/km | Send inquiry |
L02621210 | 185 mm² | 2.0 mm | 24,9 mm | 1920 kilograms/kilometer | 0.106 ohm/km | Send inquiry |
L02621810 | 240 mm² | 2,2 mm | 28,4 mm | 2260 kilograms/kilometer | 0.0801 ohm/km | Send inquiry |