XSLCH-J MOTOR 4G Cca 450/750 V
The cable complies with the requirements of the Construction Products Regulation (EU CPR 305/11) and is designed to limit the generation and spread of fire and smoke.
Shielded LSZH cables are used to power motors with frequency converters when full electromagnetic compatibility (EMC) is required.
The cable is made entirely of halogen-free material and does not release harmful substances in the event of a fire.
Suitable for static and dynamic connections (occasional movement) in industrial plants, production lines and machinery operating in normal or humid environments.
If the cable is stored/laid outdoors, it must be protected from UV exposure.
application
The cable complies with the requirements of the Construction Products Regulation (EU CPR 305/11) and is designed to limit the generation and spread of fire and smoke.
Shielded LSZH cables are used to power motors with frequency converters when full electromagnetic compatibility (EMC) is required.
The cable is made entirely of halogen-free material and does not release harmful substances in the event of a fire.
Suitable for static and dynamic connections (occasional movement) in industrial plants, production lines and machinery operating in normal or humid environments.
If the cable is stored/laid outdoors, it must be protected from UV exposure.
Direct or indirect underground installation (presence of water condition AD7).
peculiarity
-
- IEC 60228
- IEC 60332-3-24 Class C
ADDITIONAL INFORMATION
- Custom core/jacket color
Product structure
conductor | Class 5 Bare Copper Soft Conductors (IEC 60228 Class 5) |
---|---|
insulation | Cross-linked LSZH rubber composites |
color | Brown + black + gray + yellow and green |
structure | Concentric layer stranded conductors |
Wrap the bag | Full-section polyester strap |
shield | First shield:
▽ Aluminum-plastic composite belt (aluminum layer thickness≥≥0.1mm) ▽ Cover rate: ≥25% Second shield: ▽ Tinned copper woven mesh (coverage ≥85%) ▽ Purity of the tin layer ≥ 99.9% |
Sheath material: | LSZH thermoplastic composites |
Sheath color | RAL 9005 Pure Black |
Technical parameters
Operating voltage | Core operating voltage 0.6/1 kV
The outer jacket operates at 1.8kV DC and 1.2kV AC |
---|---|
Test voltage | 4000V |
Temperature range | Operating temperature range
▸ Fixed laying: -40°C ~ -5°C ▸ Non-stressed temporary mobile laying: +90°C ~ +90°C Short-circuit tolerance limit ▸ Maximum instantaneous temperature: +250°C (duration ≤5 seconds) |
environmental protection | Comply with EU RoHS directive |
Cable parameters
numbering | specification | The finished outer diameter is -ø | Max. Resistance (20° C) | |
---|---|---|---|---|
LS2380205 | 2 x 0.35 mm² | 1.8X3.7 mm | 247.0 ohm/km | Send an inquiry |
LS2380305 | 2 x 0.5 mm² | 2.1X4.2 mm | 39.0 ohm/km | Send an inquiry |
LS2380405 | 2 x 0.75 mm² | 2.3X4.6 mm | 26.0 ohm/km | Send an inquiry |
LS2380505 | 2 x 1.0 mm² | 2.4X4.8 mm | 19.5 ohm/km | Send an inquiry |
LS2380705 | 2 x 1.5 mm² | 2.9X5.8 mm | 13.3 ohm/km | Send an inquiry |
LS2381205 | 2 x 2.5 mm² | 3.3X6.6 mm | 7.98 ohm/km | Send an inquiry |