YSLY -OB/-JB/-OZ/-JZ Dca 450/750 V

The cable complies with the requirements of the Construction Products Regulation (EU CPR 305/11) and is designed to limit the generation and spread of fire and smoke.
Multi-core cables are suitable for power transmission, control, signaling, measurement or command while maintaining small size and excellent flexibility. It is used in industry for machine wiring, conveyor systems, production lines, as well as ventilation and heating systems, industrial equipment and power stations. Suitable for installation in normal or wet environments, for fixed or limited dynamic installations without mechanical stress (non-continuous movement).

application

The cable complies with the requirements of the Construction Products Regulation (EU CPR 305/11) and is designed to limit the generation and spread of fire and smoke.
Multi-core cables are suitable for power transmission, control, signaling, measurement or command while maintaining small size and excellent flexibility. It is used in industry for machine wiring, conveyor systems, production lines, as well as ventilation and heating systems, industrial equipment and power stations. Suitable for installation in normal or wet environments, for fixed or limited dynamic installations without mechanical stress (non-continuous movement).
300/500V and 450/750V (section ≤ 2.5 mm²): Underground installation is not allowed, even if protected.
0.6/1kV (section ≥ 10.00 mm²): Direct or indirect underground installation (presence of water condition AD7).

peculiarity

    • /

    ADDITIONAL INFORMATION

    • Custom core/jacket color

Product structure

conductor Class 5 Bare Copper Soft Conductors (IEC 60228 Class 5)
insulation Flame retardant PVC composite
color HD 308 S2(-OB/-JB)
structure Concentric layer stranded structure
Wrap the bag /
shield /
Sheath material: Flame retardant PVC composite
Sheath color RAL 7001 grey

Technical parameters

 

Operating voltage Core operating voltage

300/500V cross-section≤ 2.5mm²

450/750V cross-section = 4.00 and 6.00 mm²

0.6/1kV section ≥ 10.00 mm²

Outer sheath working voltage

300/500V cross-section≤ 2.5mm²

450/750V cross-section = 4.00 and 6.00 mm²

0.6/1kV section ≥ 10.00 mm²

Test voltage
  • 2000V ≤ section 2.5 mm²
  • 2500V section = 4.00 and 6.00 mm²
  • 4000V cross-section≥ 10.00 mm²
Temperature range Operating temperature range

▸ Fixed laying: -25°C ~ -5°C

▸ Non-stressed temporary mobile laying: +70°C ~ +70°C

Short-circuit tolerance limit

▸ Maximum instantaneous temperature: +160°C (duration ≤5 seconds)

environmental protection Comply with EU RoHS directive

Cable parameters

numbering specification The finished outer diameter is -ø Max. Resistance (20° C)
LS2380205 2 x 0.35 mm² 1.8X3.7 mm 247.0 ohm/km Send an inquiry
LS2380305 2 x 0.5 mm² 2.1X4.2 mm 39.0 ohm/km Send an inquiry
LS2380405 2 x 0.75 mm² 2.3X4.6 mm 26.0 ohm/km Send an inquiry
LS2380505 2 x 1.0 mm² 2.4X4.8 mm 19.5 ohm/km Send an inquiry
LS2380705 2 x 1.5 mm² 2.9X5.8 mm 13.3 ohm/km Send an inquiry
LS2381205 2 x 2.5 mm² 3.3X6.6 mm 7.98 ohm/km Send an inquiry

Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product. Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product.