FG16OHH2R16 300/500 V

The cable complies with the requirements of the Construction Products Regulation (EU CPR 305/11) and is designed to limit the generation and spread of fire and smoke.

Three-core cable with concentric shielding for power transmission and signal transmission.

It is especially used to power motors controlled by inverters/frequency converters, as well as to connect inverters to meters in factories.

Suitable for indoor fixed installations, including wet fixed installations, as well as outdoor walkways, pipes, channels, or similar facilities.

application

        • The cable complies with the requirements of the Construction Products Regulation (EU CPR 305/11) and is designed to limit the generation and spread of fire and smoke.

          Three-core cable with concentric shielding for power transmission and signal transmission.

          It is especially used to power motors controlled by inverters/frequency converters, as well as to connect inverters to meters in factories.

          Suitable for indoor fixed installations, including wet fixed installations, as well as outdoor walkways, pipes, channels, or similar facilities.

          Allows for direct or indirect underground installation.

      peculiarity

       

      • CEI 20-29 IEC 60228
      • CEI 20-11
      • CEI EN 60332-3-24 Class C IEC 60332-3-24 Class C
      • CEI 20-13 P.Q.A.

      Electromagnetic shielding performance: Concentric shielding structure effectively suppresses high-frequency interference (according to EN 50288-7)

      Environmental Adaptability:

      Operating temperature range: -15°C to +90°C

      Oil resistance: Tested according to CEI EN 60811-404

      ADDITIONAL INFORMATION

      • Customizable core/sheath color

      Product structure

      conductor Three-core symmetrical structure
      insulation HEPR rubber-based compound, G16 mass
      color Conductor colour scale: DIN 47100 standard
      structure Concentric layer stranded structure
      Wrap the bag Full section polyester strap wrapping
      shield The first shield is aluminum-plastic composite belt (fully covered) with a thickness of ≥0.1mm

      Second shield Tinned copper braided mesh (coverage ≥85%)

      Cross-sectional area requirements:

      • ≤16mm²: equal to the cross-sectional area of the phase line

      • ≥ 25mm²: ≥16mm² or 50% of the phase cross-sectional area

      Sheath material: PVC mixed material, R16 grade, oil resistance according to CEI EN 60811-404
      Sheath color RAL 7035 standard grey

      Technical parameters

       

      Operating voltage The core operating voltage is 0.6/1kV

      The working voltage of the outer sheath is 0.6/1kV

      Test voltage Test voltage 4000V
      Temperature range Operating temperature range: -15°C to +90°C

      Oil resistance: Tested according to CEI EN 60811-404

      environmental protection Comply with EU RoHS directive

Cable parameters

numbering specification The finished outer diameter is -ø Max. Resistance (20° C)
LS2380205 2 x 0.35 mm² 1.8X3.7 mm 247.0 ohm/km Send an inquiry
LS2380305 2 x 0.5 mm² 2.1X4.2 mm 39.0 ohm/km Send an inquiry
LS2380405 2 x 0.75 mm² 2.3X4.6 mm 26.0 ohm/km Send an inquiry
LS2380505 2 x 1.0 mm² 2.4X4.8 mm 19.5 ohm/km Send an inquiry
LS2380705 2 x 1.5 mm² 2.9X5.8 mm 13.3 ohm/km Send an inquiry
LS2381205 2 x 2.5 mm² 3.3X6.6 mm 7.98 ohm/km Send an inquiry

Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product. Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product.

Recently viewed products