FG16OR16NR16 300/500 V

The cable complies with the requirements of the Construction Products Regulation (EU CPR 305/11) and is designed to limit the generation and spread of fire and smoke.

Armored multi-core cables for power, signal and control, insulated with high modulus ethylene polypropylene rubber.

Suitable for indoor installation, even in wet environments, and outdoors.

Ideal for fixing on masonry and metal structures or hanging installations.

Galvanized steel strip reinforcement provides exceptional mechanical protection and strength, making it particularly suitable for industrial environments with high operating conditions.

application

The cable complies with the requirements of the Construction Products Regulation (EU CPR 305/11) and is designed to limit the generation and spread of fire and smoke.

Armored multi-core cables for power, signal and control, insulated with high modulus ethylene polypropylene rubber.

Suitable for indoor installation, even in wet environments, and outdoors.

Ideal for fixing on masonry and metal structures or hanging installations.

Galvanized steel strip reinforcement provides exceptional mechanical protection and strength, making it particularly suitable for industrial environments with high operating conditions.

Allows for direct or indirect underground installation.

peculiarity

 

  • CEI 20-29 IEC 60228
  • CEI 20-11 
  • CEI EN 60332-3-24 Cat.C IEC 60332-3-24 Cat.C
  • CEI 20-13 P.Q.A.

ADDITIONAL INFORMATION

  • Customizable core/sheath color

Product structure

conductor Bare copper wire complies with IEC 60228, VDE 0295, class 5 standards
insulation HEPR Rubber Compound (G16 Grade)
color Conductor colour scale: CEI UNEL 00722 – 00725 (HD 308 S2 – EN 50334)
structure Concentric layer stranded structure
Wrap the bag Monolith polyester strap wrap
shield Integral steel belt armor
Sheath material: PVC mixed material, R16 grade, oil resistance according to CEI EN 60811-404
Sheath color Outer sheath colour: RAL 7035 standard grey

Technical parameters

 

Operating voltage The core operating voltage is 0.6/1kV

The working electricity of the outer sheath is 0.6/1kV

Test voltage 4000V
Temperature range Minimum operating temperature -15°C long-term operation allowance

Maximum operating temperature +90°C long-term operation allowance

Short-circuit withstand temperature +250°C for a duration of ≤5 seconds

environmental protection Comply with EU RoHS directive

Cable parameters

numbering specification The finished outer diameter is -ø Max. Resistance (20° C)
LS2380205 2 x 0.35 mm² 1.8X3.7 mm 247.0 ohm/km Send an inquiry
LS2380305 2 x 0.5 mm² 2.1X4.2 mm 39.0 ohm/km Send an inquiry
LS2380405 2 x 0.75 mm² 2.3X4.6 mm 26.0 ohm/km Send an inquiry
LS2380505 2 x 1.0 mm² 2.4X4.8 mm 19.5 ohm/km Send an inquiry
LS2380705 2 x 1.5 mm² 2.9X5.8 mm 13.3 ohm/km Send an inquiry
LS2381205 2 x 2.5 mm² 3.3X6.6 mm 7.98 ohm/km Send an inquiry

Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product. Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product.