FG16R16 600/1000 V

FG16 cables are suitable for indoor and outdoor installations, including wet environments. It can be fixed on exposed surfaces or metal structures, and can also be laid directly in the ground.

This type of cable is suitable for general construction scenarios where fire resistance is required. According to CEI 64 – 8:V4 Section 751.04.2.8.a, the fire protection class reaches CCA-S3,D1,A3 when installed in bundles in places with a high risk of fire.

application

FG16 cables are suitable for indoor and outdoor installations, including wet environments. It can be fixed on exposed surfaces or metal structures, and can also be laid directly in the ground.


This type of cable is suitable for general construction scenarios where fire resistance is required. According to CEI 64 – 8:V4 Section 751.04.2.8.a, the fire protection class reaches CCA-S3,D1,A3 when installed in bundles in places with a high risk of fire.


For more information and advice on the use of these cables, see the CEI 20 – 67 standard.

Certifications and standards

 

  • CEI 20-13; – CEI UNEL 35324;  – CEI 20-11;  – CEI EN/IEC 60228; – CEI EN 50399;  – EN 60754-2;  – EN 61034-2; – CEI EN/IEC 60332-1-2;  – EN 13501-6
  • Low Voltage DC 2006/95/EC,
  • ROHS DC 2002/95/EC certification

ADDITIONAL INFORMATION

 

 

  • Can be customized Core Count X1.5mm² + Core Count X 0.34mm²
  • For example: 4*1.5mm²+4X0.34mm²
  • Custom splices, wiring harnesses, etc

Product structure

conductor Class 5 soft-annealed oxygen-free copper stranded wire in accordance with CEI EN/IEC 60228
insulation G16 Quality High Modulus Ethylene Propylene Rubber (HEPR)
color black
shield not
Sheath material: R16 type polyvinyl chloride
Sheath color Grey (RAL 7001), other colours available

Technical parameters

Nominal voltage 600/1000 V
Test voltage 2000V
Bending radius Fixed laying: 4xd
Flame retardant IEC 60332.1
Temperature range Fixed application: -15/+80°C

Flexible application: +5/+70°C

Large short circuit temperature: 250°C

Tensile resistance 5 Kg / mm2
environmental protection Comply with EU RoHS directive

Cable parameters

numbering specification Insulation thickness Outer diameter – ø Cable weight ≈ Max. Resistance (20° C)
L02621007 1  mm² 0,7 mm 7.5 mm 79 kg/km 18.5 ohm/km Send an inquiry
L02621507 1.5 mm² 0,7 mm 8.2 mm 94 kg/km 12.1 ohm/km Send an inquiry
L02622507 2.5 mm² 0,7 mm 8.7 mm 112 kg/km 7.41 ohm/km Send an inquiry
L02624007 4 mm² 0,7 mm 9.3 mm 139 kg/km 4.61 ohm/km Send an inquiry
L02626007 6 mm² 0,7 mm 9.9 mm 188 kg/km 3.08 ohm/km Send an inquiry
L02610007 10 mm² 0,7 mm 10.9 mm 227 kg/km 1.83 ohm/km Send an inquiry
L02616007 16 mm² 0,9 mm 11.4 mm 331 kg/km 1.15 ohm/km Send an inquiry
L02625007 25 mm² 0,9 mm 13.2 mm 425 kg/km 0.727 ohm/km Send an inquiry
L02623507 35 mm² 1,0 mm 14.6 mm 579 kg/km 0.524 ohm/km Send an inquiry
L02650000 50 mm² 1,1mm 16.4 mm 784 kg/km 0.387 ohm/km Send an inquiry
L02670000 70 mm² 1,1 mm 18.3 mm 989 kg/km 0.272 ohm/km Send an inquiry
L02695000 95 mm² 1,2 mm 22.4 mm 1250 kg/km 0.206 ohm/km Send an inquiry
L02120000 120 mm² 1,4 mm 24.8 mm 1540 kg/km 0.161 ohm/km Send an inquiry
L02150000 150 mm² 1,6 mm 27.2 mm 1890 kg/km 0.128 ohm/km Send an inquiry
L02185000 185 mm² 1,7 mm 30.4 mm 2410 kg/km 0.106 ohm/km Send an inquiry
L02240000 240 mm² 1,7 mm 33.0 mm 3030 kg/km 0.0801 ohm/km Send an inquiry

Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product. Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product.