FG16XHOHM16 Cca 300/300 V

The cable complies with the requirements of the Building Products Regulation (CPR EU 305/11) and is designed to limit the generation and spread
of fire and smoke Multiple pairs of cables are shielded on each individual pair of cables for data transmission between the central unit and peripherals and for interconnections between equipment that require high-quality transmission signals.
Suitable for indoor fixed installations, even if wet, for outdoor walkways, pipes, channels or similar.

application

The cable complies with the requirements of the Building Products Regulation (CPR EU 305/11) and is designed to limit the generation and spread
of fire and smoke Multiple pairs of cables are shielded on each individual pair of cables for data transmission between the central unit and peripherals and for interconnections between equipment that require high-quality transmission signals.
Suitable for indoor fixed installations, even if wet, for outdoor walkways, pipes, channels or similar.
If cables are stored/laid outdoors, they must be protected from UV exposure. Direct or indirect underground installation
is allowed

peculiarity

 

  • CEI 20-29 IEC 60228
  • CEI 20-11
  • CEI EN 60332-3-24 Cat.C IEC 60332-3-24 Cat.C
  • CEI 20-13 P.Q.A

ADDITIONAL INFORMATION

  • The cable adopts a three-wire group structure
  • The outer sheath is available in blue or black
  • Support conductor color customization (e.g., white + black combination, black conductor with sequence numbering)

Product structure

conductor Tinned soft copper wire complies with IEC 60228, VDE 0295, Class 5
insulation HEPR rubber-based compound, G16 grade
color Blue + Black (black conductor with sequential numbering)
structure Twisted pair

Concentric layer stranded wire pairs

Wrap the bag First layer of wrap protection:

Single thread to polyester strap covering

Second layer of wrap protection:

Integral polyester strap covering

shield First layer of shielding:

Single wire shielded with aluminum/polyester with tinned soft copper streamline

Second layer of shielding:

Integral aluminum/polyester shielding with tinned soft copper streamline

Sheath material: LSZH thermoplastic material-based mixture, M16 grade, oil and hydrocarbon resistant
Sheath color Green (according to RAL 6024)

Technical parameters

 

Operating voltage The core operating voltage is 0.6/1kV

The working electricity of the outer sheath is 0.6/1kV

Test voltage 4000V
Temperature range Minimum operating temperature -40°C

Maximum operating temperature +90°C

Short-circuit withstand temperature +250°C

environmental protection Comply with EU RoHS directive

Cable parameters

numbering specification The finished outer diameter is -ø Max. Resistance (20° C)
LS2380205 2 x 0.35 mm² 1.8X3.7 mm 247.0 ohm/km Send an inquiry
LS2380305 2 x 0.5 mm² 2.1X4.2 mm 39.0 ohm/km Send an inquiry
LS2380405 2 x 0.75 mm² 2.3X4.6 mm 26.0 ohm/km Send an inquiry
LS2380505 2 x 1.0 mm² 2.4X4.8 mm 19.5 ohm/km Send an inquiry
LS2380705 2 x 1.5 mm² 2.9X5.8 mm 13.3 ohm/km Send an inquiry
LS2381205 2 x 2.5 mm² 3.3X6.6 mm 7.98 ohm/km Send an inquiry

Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product. Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product.