FG17 450/750 V
Suitable for installation in pipes or embedded conduits, or similar closed systems; Suitable for fixed protective installations in or over lighting or control equipment up to 1000 volts AC and 750 volts DC to ground. It is not suitable for laying directly or indirectly underground, and is not suitable for laying outdoors, in humid environments, under unprotected conditions, and buried under plaster.
It is suitable for general applications in construction projects and meets the requirements of fire prevention. Suitable for bundle installation with a high fire risk, fire rating CCA – S1B, D1, A1.
application
Suitable for installation in pipes or embedded conduits, or similar closed systems; Suitable for fixed protective installations in or over lighting or control equipment up to 1000 volts AC and 750 volts DC to ground. It is not suitable for laying directly or indirectly underground, and is not suitable for laying outdoors, in humid environments, under unprotected conditions, and buried under plaster.
It is suitable for general applications in construction projects and meets the requirements of fire prevention. Suitable for bundle installation with a high fire risk, fire rating CCA – S1B, D1, A1.
Further instructions and guidance are available in CEI EN 50565 – 1, CEI EN 50565 – 2 and CEI 20 – 40.
Function
- – CEI-UNEL 35716;
- – IEC EN/IEC 60228;
- – IEC EN/IEC 60332-1-2;
- – IEC EN 50267-2-1;
- – CPR EN 50399
- – IEC EN 50525-1 p.q.a./a.p.;
- – IEC EN 50525-2-31 p.q.a./ a.p.;
- – CEI EN 60754-2; EN 61034-2;
- – EN 50575:2014+A1:2016;
- – IEC 64-8:V4.
Additional information
- Customizable colors
- Customizable to adapt to higher temperatures
Product structure
Conductor |
|
|
---|---|---|
Insulation | G17 quality rubber | |
Insulation color | Blue, dark blue, light blue, black, brown, gray, yellow/green, red, white, cyan, purple, orange, pink |
Technical parameters
Working voltage | Uo/U 450 / 750V |
---|---|
Test voltage | 2000 volts |
Bending radius | ≥ 10 square millimeters, 4 *D
Other cases are 6 *D |
Temperature range | Fixed laying: -30/+80°C
Flexible application: -5/+70°C Short-circuit maximum temperature; 250°C |
Tensile strength | 1.5 kilograms/square millimeter |
No halogen | CEI EN 50565 – 1, EN 50565-2 |
Fire resistance | Flame retardant and self-extinguishing, in accordance with IEC 60332-1-2 + VDE 0482-332-1-2 standard |
Oil resistance | Understand internal standards |
Executive Standard | 2014/35/UE (B.T.) – 2011/65/CE ; 2015/863/UE(RoHS); 305/2011 EU |
Environmental protection | Complies withEURoHS directive |
Cable parameters
Number | Specifications | Insulation thickness | Outer diameter – ø | Cable weight ≈ | Maximum resistance (20°C) | |
---|---|---|---|---|---|---|
L02620207 | 1 square millimeter | 0.7 mm | 3,0 mm | 15 kilograms/kilometer | 19.5 ohms/kilometer | Send inquiry |
L02620307 | 1.5 square millimeters | 0.7 mm | 3.4 mm | 21 kilograms/kilometer | 13.3 Ohm/km | Send inquiry |
L02620407 | 2.5 mm² | 0.8 mm | 4,1 mm | 32 kilograms/kilometer | 7.98 ohms/km | Send inquiry |
L02620507 | 4 square millimeters | 0.8 mm | 4.8 mm | 47 kilograms/kilometer | 4.95 ohms/km | Send inquiry |
L02620707 | 6 square millimeters | 0.8 mm | 5,3 mm | 65 kilograms/kilometer | 3.30 Ohm/km | Send inquiry |
L02621207 | 10 square millimeters | 1,0 millimeters | 6,8 mm | 110 kilograms/kilometer | 19.1 Ohm/km | Send inquiry |
L02621807 | 16 square millimeters | 1,0 millimeters | 8,1 mm | 170 kilograms/kilometer | 1.21 Ohm/km | Send inquiry |
L02622007 | 25 square millimeters | 1,2 mm | 10,2 mm | 255 kilograms/kilometer | 0.78 Ohm/km | Send inquiry |
L02622507 | 35 square millimeters | 1,2 mm | 11.7 mm | 345 kilograms/kilometer | 0.554 ohm/kilometer | Send inquiry |
L02620210 | 50 square millimeters | 1,4 mm | 13,9 mm | 495 kilograms/kilometer | 0.386 ohm/km | Send inquiry |
L02620310 | 70 mm² | 1,4 mm | 16,0 mm | 680 kilograms/kilometer | 0.272 ohms/kilometer | Send inquiry |
L02620410 | 95 square millimeters | 1.6 mm | 18,2 mm | 900 kilograms/kilometer | 0.206 ohm/km | Send inquiry |
L02620510 | 120 mm² | 1.6 mm | 20,2 mm | 1135 kilograms/kilometer | 0.161 Ohm/km | Send inquiry |
L02620710 | 150 mm² | 1.8mm | 22.5 mm | 1412 kilograms/kilometer | 0.128 Ohm/km | Send inquiry |
L02621210 | 185 mm² | 2.0 mm | 24,9 mm | 1920 kilograms/kilometer | 0.106 ohm/km | Send inquiry |
L02621810 | 240 mm² | 2,2 mm | 28,4 mm | 2260 kilograms/kilometer | 0.0801 ohm/km | Send inquiry |