FG18M16 600/1000 V
It is suitable for bundle installation in high-risk fire environments, including places with high concentration of people for a long time, or places with serious potential harm to animals, such as air terminals, railway stations, port passenger stations, subways, highways and railways, tunnels, etc. Its fire resistance complies with the requirements of section 3a of CEI 64 – 8:V4 751.04 3a, and for cables installed in railway tunnels, it is rated B2CA – S1a, D1, A1 and complies with EU Regulation 1303/2014, as provided by the regulation.
Suitable for indoor or outdoor environments, including wet environments, these cables can be fixed in open air environments, inside pipes, masonry, metal structures or suspended installations, and also allow buried installations.
application
It is suitable for bundle installation in high-risk fire environments, including places with high concentration of people for a long time, or places with serious potential harm to animals, such as air terminals, railway stations, port passenger stations, subways, highways and railways, tunnels, etc. Its fire resistance complies with the requirements of section 3a of CEI 64 – 8:V4 751.04 3a, and for cables installed in railway tunnels, it is rated B2CA – S1a, D1, A1 and complies with EU Regulation 1303/2014, as provided by the regulation.
For more instructions and warnings on the use of these cables, see CEI 20 – 67.
Certifications and standards
- CEI 20-22/2 , CEI 20-34, CEI 20-37, CEI 20-20/1/2, EN 50265, HD 21.5 Sez. 3, IEC 60332-3– CEI-UNEL 35716; – CEI EN/IEC 60228; – CEI EN/IEC 60332-1-2; – CEI EN 50267-2-1; – CPR EN 50399 – CEI EN 50525-1 p.q.a./a.p.; – CEI EN 50525-2-31 p.q.a./ a.p.; – CEI EN 60754-2; EN 61034-2; – EN 50575:2014+A1:2016; – CEI 64-8:V4.
- Low Voltage DC 2006/95/EC,
- ROHS DC 2002/95/EC certification
ADDITIONAL INFORMATION
- Can be customized Core Count X1.5mm² + Core Count X 0.34mm²
- For example: 4*1.5mm²+4X0.34mm²
- Custom splices, wiring harnesses, etc
Product structure
conductor | Class 5 soft-annealed oxygen-free copper wire in soft stranded form, CEI EN/IEC 60228 standard |
---|---|
insulation | G18 quality rubber |
color | Color coded to HD-308/EN50334, yellow-green ground wire (3-core and above) |
shield | not |
Sheath material: | M16 quality thermoplastic composites |
Sheath color | Black (RAL 9005), other colours available |
Technical parameters
Nominal voltage | 600/1000 V |
---|---|
Test voltage | Core/Core 2000/2000 |
Bending radius | Fixed laying: 4xd
Flexible application: 6 xd |
Flame retardant | IEC 60332.1 |
Temperature range | Fixed laying: -20/+80°C
Flexible application: +5/+70°C |
Tensile resistance | 5 Kg / mm2 |
environmental protection | Comply with EU RoHS directive |
Cable parameters
numbering | specification | Insulation thickness | Outer diameter – ø | Cable weight ≈ | Max. Resistance (20° C) | |
---|---|---|---|---|---|---|
L02621007 | 1 mm² | 1,0 mm | 8.4 mm | 70 kg/km | 19.5 ohm/km | Send an inquiry |
L02621507 | 1.5 mm² | 1,0 mm | 8.9 mm | 75 kg/km | 13.3 ohm/km | Send an inquiry |
L02622507 | 2.5 mm² | 1,0 mm | 9.4 mm | 90 kg/km | 7.98ohm/km | Send an inquiry |
L02624007 | 4 mm² | 1,0 mm | 10 mm | 105 kg/km | 4.95 ohm/km | Send an inquiry |
L02626007 | 6 mm² | 1,0 mm | 10.9 mm | 130 kg/km | 3.30 ohm/km | Send an inquiry |
L02610007 | 10 mm² | 1,0 mm | 11.9 mm | 189 kg/km | 19.1 ohm/km | Send an inquiry |
L02616007 | 16 mm² | 1,2 mm | 13.8 mm | 228 kg/km | 1.21 ohm/km | Send an inquiry |
L02625007 | 25 mm² | 1,2 mm | 15.1 mm | 332 kg/km | 0.78 ohm/km | Send an inquiry |
L02623507 | 35 mm² | 1,4 mm | 17.2 mm | 426 kg/km | 0.554 ohm/km | Send an inquiry |
L02650000 | 50 mm² | 1,4 mm | 19.1 mm | 580 kg/km | 0.386 ohm/km | Send an inquiry |
L02670000 | 70 mm² | 1,6 mm | 16,0 mm | 785 kg/km | 0.272 ohm/km | Send an inquiry |
L02695000 | 95 mm² | 1,6 mm | 21.6 mm | 990 kg/km | 0.206 ohm/km | Send an inquiry |
L02120000 | 120 mm² | 1,8 mm | 23.7 mm | 1250 kg/km | 0.161 ohm/km | Send an inquiry |
L02150000 | 150 mm² | 1,8 mm | 25,5 mm | 1540 kg/km | 0.128 ohm/km | Send an inquiry |
L02185000 | 185 mm² | 2,0 mm | 27,9 mm | 1920 kg/km | 0.106 ohm/km | Send an inquiry |
L02240000 | 240 mm² | 2,2 mm | 30.7 mm | 2260 kg/km | 0.0801 ohm/km | Send an inquiry |