FROR16 O.R. DIN 300/500 V
Fixed laying cables that comply with the requirements of the EU Construction Products Regulation (CPR EU 305/11) with flame retardant and smoke suppression properties.
Multi-core control cables for signal transmission, control loops and measurement systems, equipped with oil-resistant outer sheaths. Its low-smoke halogen-free characteristics (low fire risk when laid in bundles) and compact construction make it particularly suitable for building intercom systems, civil/industrial indoor wiring and internal connections of equipment.
It can coexist with 450/750V power cables. When used for power supply in Class 0 systems (AC rated voltage ≤50V or DC/ripple-free voltage ≤120V), it can also coexist and lay with 0.6/1kV (230/400V rated voltage) power cables. However, it is necessary to pay attention to possible electromagnetic interference problems.
application
Fixed laying cables that comply with the requirements of the EU Construction Products Regulation (CPR EU 305/11) with flame retardant and smoke suppression properties.
Multi-core control cables for signal transmission, control loops and measurement systems, equipped with oil-resistant outer sheaths. Its low-smoke halogen-free characteristics (low fire risk when laid in bundles) and compact construction make it particularly suitable for building intercom systems, civil/industrial indoor wiring and internal connections of equipment.
It can coexist with 450/750V power cables. When used for power supply in Class 0 systems (AC rated voltage ≤50V or DC/ripple-free voltage ≤120V), it can also coexist and lay with 0.6/1kV (230/400V rated voltage) power cables. However, it is necessary to pay attention to possible electromagnetic interference problems.
Allowed for non-stressed temporary mobile laying scenarios.
It is strictly forbidden to lay directly buried (including protection) and permanent outdoor laying (including protection).
peculiarity
- CEI 20-29/IEC 60228
- CEI 20-11
- CEI EN 60332-3-24 Cat.C/IEC 60332-3-24 Cat.C
- CEI UNEL 36762
- CEI EN 60811-404
ADDITIONAL INFORMATION
- Customizable core/sheath color
Product structure
conductor | Bare copper wire complies with IEC 60228, VDE 0295, class 5 standards |
---|---|
insulation | PVC mixed material, R2 grade |
color | CEI UNEL 00722 – 00725 (for HD 308 S2 – EN50334) |
structure | Concentric layer stranded structure |
Wrap the bag | not |
shield | not |
Sheath material: | PVC mixed material, R16 grade, oil resistance according to CEI EN 60811-404 |
Sheath color | RAL 7035 grey |
Technical parameters
Operating voltage | ≤0.75mm² cross-section: 300/500V
≥ 1.00 mm² cross-section: 450/750 V |
---|---|
Test voltage | ≤0.75mm² cross-section: 2000V
≥ 1.00mm² cross-section: 2500V |
Temperature range | Fixed laying: -25°C to +70°C
Non-stressed temporary mobile laying: -5°C to +70°C Short-circuit tolerance temperature +160°C (max) |
environmental protection | Comply with EU RoHS directive |
Cable parameters
numbering | specification | The finished outer diameter is -ø | Max. Resistance (20° C) | |
---|---|---|---|---|
LS2380205 | 2 x 0.35 mm² | 1.8X3.7 mm | 247.0 ohm/km | Send an inquiry |
LS2380305 | 2 x 0.5 mm² | 2.1X4.2 mm | 39.0 ohm/km | Send an inquiry |
LS2380405 | 2 x 0.75 mm² | 2.3X4.6 mm | 26.0 ohm/km | Send an inquiry |
LS2380505 | 2 x 1.0 mm² | 2.4X4.8 mm | 19.5 ohm/km | Send an inquiry |
LS2380705 | 2 x 1.5 mm² | 2.9X5.8 mm | 13.3 ohm/km | Send an inquiry |
LS2381205 | 2 x 2.5 mm² | 3.3X6.6 mm | 7.98 ohm/km | Send an inquiry |