FTE29OHM16 100/100 V

They can be used to connect equipment with automatic fixed detection systems and manual fire alarm systems, whether these systems are connected to fire extinguishing systems or other (active or passive) protection systems, and are suitable for installation in buildings of all kinds of applications. However, they are not suitable for other uses, such as emergency lighting, power supply of forced smoke and heat exhaust systems, electronic locks or emergency controls, and other similar applications where the voltage is greater than 100 volts AC.

 

FTE29OHM16 – 100/100V cables are marked CEI 20 – 105 (PH 120), indicating that they are fireproof according to CEI EN 50200 and that the cable under test will maintain an uptime of at least 120 minutes under open flame and mechanical shock at 820°C

application

They can be used to connect equipment with automatic fixed detection systems and manual fire alarm systems, whether these systems are connected to fire extinguishing systems or other (active or passive) protection systems, and are suitable for installation in buildings of all kinds of applications. However, they are not suitable for other uses, such as emergency lighting, power supply of forced smoke and heat exhaust systems, electronic locks or emergency controls, and other similar applications where the voltage is greater than 100 volts AC.


FTE29OHM16 – 100/100V cables are marked CEI 20 – 105 (PH 120), indicating that they are fireproof according to CEI EN 50200 and that the cable under test will maintain an uptime of at least 120 minutes under open flame and mechanical shock at 820°C

Certifications and standards

 

  • CEI 20-22/2 , CEI 20-34, CEI 20-37, CEI 20-20/1/2, EN 50265, HD 21.5 Sez. 3, IEC 60332-3– CEI-UNEL 35716; – CEI EN/IEC 60228; – CEI EN/IEC 60332-1-2;  – CEI EN 50267-2-1; – CPR EN 50399 – CEI EN 50525-1 p.q.a./a.p.;  – CEI EN 50525-2-31 p.q.a./ a.p.; – CEI EN 60754-2; EN 61034-2; – EN 50575:2014+A1:2016; – CEI 64-8:V4.
  • Low Voltage DC 2006/95/EC,
  • ROHS DC 2002/95/EC certification

ADDITIONAL INFORMATION

 

 

  • Can be customized Core Count X1.5mm² + Core Count X 0.34mm²
  • For example: 4*1.5mm²+4X0.34mm²
  • Custom splices, wiring harnesses, etc

Product structure

conductor Class 5 soft annealed red copper stranded wire covered with mica belt with fire protection function, CEI EN/IEC 60228 standard
insulation Thermoplastic polyolefin S29 is used
Insulation color Black, red
shield Aluminium / polyester strap with tinned copper drain wire
Sheath material: M16 quality thermoplastic mix
Sheath color Red (RAL 3000) or purple (RAL 4008), other colours are available

Technical parameters

Nominal voltage Uo/U 100/100 V
Test voltage Core/Core 1000V
Bending radius Fixed laying: 14xD
Temperature range Fixed laying: -25/+90°C, temperature reachable in case of short circuit: +250º C
No halogen

Insulation resistance

Complies with IEC 60754-1, EN 50267-2-1

10 MΩ x km

Fire resistance Flame retardant: CEI 20-22 II, IEC 60332-3-C
Corrosiveness of combustion gases No corrosive combustion gases are produced IEC 60754-2, EN 50267-2-2

Low smoke density: IEC 61034, EN 50268-2

environmental protection Comply with EU RoHS directive

Cable parameters

numbering specification The finished outer diameter is -ø Cable weight ≈ Max. Resistance (20° C)
LS2380205 2 x 0,5 mm² 17.9 mm 62 kg/km 39 ohm/km Send an inquiry
LS2380305 2 x 0,75 mm² 18.1 mm 71 kg/km 26 ohm/km Send an inquiry
LS2380405 2 x 1 mm² 18.6 mm 380 kg/km 19.5 ohm/km Send an inquiry
LS2380505 2 x 1.5 mm² 9.7 mm 104 kg/km 13.3 ohm/km Send an inquiry
LS2380705 2 x 2.5 mm² 11.6 mm 155 kg/km 7.98 ohm/km Send an inquiry