H07BQ-F Fca 450/750 V

The cable complies with the requirements of the Construction Products Regulation (EU CPR 305/11) and is designed to limit the generation and spread of fire and smoke.
Flexible cable for heavy mobile service that can be installed in dry or wet places as well as outdoors.
It can be used for connections that withstand moderate mechanical stress, such as power tools, motors, or machines that can be transported on construction sites or in agricultural applications.
Suitable for refrigeration and heating equipment applications, as long as they do not come into contact with hot parts and are not exposed to thermal radiation.
It is particularly suitable for situations where cables are subjected to high wear and tear stress. It can also
be used for fixed installation.

application

The cable complies with the requirements of the Construction Products Regulation (EU CPR 305/11) and is designed to limit the generation and spread of fire and smoke.
Flexible cable for heavy mobile service that can be installed in dry or wet places as well as outdoors.
It can be used for connections that withstand moderate mechanical stress, such as power tools, motors, or machines that can be transported on construction sites or in agricultural applications.
Suitable for refrigeration and heating equipment applications, as long as they do not come into contact with hot parts and are not exposed to thermal radiation.
It is particularly suitable for situations where cables are subjected to high wear and tear stress. It can also
be used for fixed installation.
Even if protected, it is not allowed to lay underground.

peculiarity

    • IEC 60228
    • EN 50525-2-21
    • EN 50363

    ADDITIONAL INFORMATION


    • Black, yellow or gray
    • The structure/section does not meet the requirements of the 50525-2-21 standard

Product structure

conductor Bare copper wire complies with IEC 60228, VDE 0295, class 5 standards
insulation EI6 grade rubber matrix composites
color Compliant with CEI UNEL 00722 (HD 308 S2) specifications
structure Concentric layer stranding (with padding structure)
Wrap the bag /
shield /
Sheath material: Thermoplastic polyurethane (TMPU) material
Sheath color Orange (RAL 2004 standard colour)

Technical parameters

 

Operating voltage The core working voltage is 450/750V

The outer sheath works with electricity 450/750V

Test voltage 2500V
Temperature range Minimum operating temperature -50°C

Maximum operating temperature +90°C

Short-circuit tolerance temperature +250°C (max)

environmental protection Comply with EU RoHS directive

Cable parameters

numbering specification The finished outer diameter is -ø Max. Resistance (20° C)
LS2380205 2 x 0.35 mm² 1.8X3.7 mm 247.0 ohm/km Send an inquiry
LS2380305 2 x 0.5 mm² 2.1X4.2 mm 39.0 ohm/km Send an inquiry
LS2380405 2 x 0.75 mm² 2.3X4.6 mm 26.0 ohm/km Send an inquiry
LS2380505 2 x 1.0 mm² 2.4X4.8 mm 19.5 ohm/km Send an inquiry
LS2380705 2 x 1.5 mm² 2.9X5.8 mm 13.3 ohm/km Send an inquiry
LS2381205 2 x 2.5 mm² 3.3X6.6 mm 7.98 ohm/km Send an inquiry

Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product. Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product.