LiHCH-DIN B2ca 450/750 V

The cable complies with the requirements of the Construction Products Regulation (EU CPR 305/11) and is designed to limit the generation and spread of fire and smoke.
Shielded LSZH cables are used for data transmission in electronics and computers for signaling, measurement, command or control systems, as well as in general applications that require effective protection from external electromagnetic interference and small size. It is especially suitable for places with fire risk and dense crowds, such as schools, offices, theaters, hospitals, etc.
Suitable for installation in normal or wet environments for fixed or limited dynamic installations (non-continuous motion) without mechanical stress.

application

The cable complies with the requirements of the Construction Products Regulation (EU CPR 305/11) and is designed to limit the generation and spread of fire and smoke.
Shielded LSZH cables are used for data transmission in electronics and computers for signaling, measurement, command or control systems, as well as in general applications that require effective protection from external electromagnetic interference and small size. It is especially suitable for places with fire risk and dense crowds, such as schools, offices, theaters, hospitals, etc.
Suitable for installation in normal or wet environments for fixed or limited dynamic installations (non-continuous motion) without mechanical stress.
If the cable is stored/laid outdoors, it must be protected from UV exposure. Even if it is protected, it is not allowed to lay underground.

peculiarity

    • IEC 60228
    • IEC 60332-3-24 Class C

    ADDITIONAL INFORMATION

    • Custom core/jacket color

Product structure

conductor Class 5 Bare Copper Soft Conductors (IEC 60228 Class 5)
insulation LSZH thermoplastic composites
color DIN 47100 standard
structure Concentric layer stranded conductors

Wrap the bag Full-section polyester strap
shield Full section tinned copper woven mesh
Sheath material: LSZH thermoplastic composites
Sheath color RAL 7001 grey

Technical parameters

 

Operating voltage Core operating voltage

300V cross-section≤0.75 mm²

500V cross-section ≥1.00 mm²

Outer sheath working voltage

450/750V

Test voltage 2000V cross-section≤0.75

mm²

2500V cross-section≥1.00 mm²

Temperature range Operating temperature range

▸ Fixed laying: -40°C ~ -5°C

▸ Non-stressed temporary mobile laying: +70°C ~ +70°C

Short-circuit tolerance limit

▸ Maximum instantaneous temperature: +160°C (duration ≤5 seconds)

environmental protection Comply with EU RoHS directive

Cable parameters

numbering specification The finished outer diameter is -ø Max. Resistance (20° C)
LS2380205 2 x 0.35 mm² 1.8X3.7 mm 247.0 ohm/km Send an inquiry
LS2380305 2 x 0.5 mm² 2.1X4.2 mm 39.0 ohm/km Send an inquiry
LS2380405 2 x 0.75 mm² 2.3X4.6 mm 26.0 ohm/km Send an inquiry
LS2380505 2 x 1.0 mm² 2.4X4.8 mm 19.5 ohm/km Send an inquiry
LS2380705 2 x 1.5 mm² 2.9X5.8 mm 13.3 ohm/km Send an inquiry
LS2381205 2 x 2.5 mm² 3.3X6.6 mm 7.98 ohm/km Send an inquiry

Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product. Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product.