LiYCY-TP-DIN PRIME Cca 450/750 V
The cables meet the requirements in the Construction Products Regulation (CPR EU 305/11) and are designed to limit the generation and spread of fire and smoke.
Multiple pairs of cables for data transmission in electronics and computers for signaling, measurement, command and control systems, and more generally for applications that require effective protection from external electromagnetic interference and compact size.
Suitable for installation in dry or humid indoor environments, for static or limited dynamic installations (non-permanent motion) without mechanical stress. Even if it is protected, it is not allowed to lay underground.
application
The cables meet the requirements in the Construction Products Regulation (CPR EU 305/11) and are designed to limit the generation and spread of fire and smoke.
Multiple pairs of cables for data transmission in electronics and computers for signaling, measurement, command and control systems, and more generally for applications that require effective protection from external electromagnetic interference and compact size.
Suitable for installation in dry or humid indoor environments, for static or limited dynamic installations (non-permanent motion) without mechanical stress. Even if it is protected, it is not allowed to lay underground.
peculiarity
-
- IEC 60228
- IEC 60332-3-24 Class C
ADDITIONAL INFORMATION
- Custom core/jacket color
Product structure
conductor | Class 5 Bare Copper Soft Conductors (IEC 60228 Class 5)
Minimum bending radius: 6× cable outer diameter |
---|---|
insulation | Flame retardant PVC composite (tested by IEC 60332-1-2) |
color | Compliant with DIN 47100 full chromatography |
structure | Twisted in pairs IEC61156
Total stranded Concentric layers HD 18 |
Wrap the bag | / |
shield | Shielding Type: Tinned copper braid
Coverage: ≥85% Resistivity: ≤25Ω/km |
Sheath material: | Flame retardant PVC compound
Thickness: ≥1.5mm (in accordance with IEC 60502-1) Oxygen Index: ≥32% |
Sheath color | RAL 7001 Grey (ΔE≤2.0) |
Technical parameters
Operating voltage | The core working voltage is 300/500V
Outer sheath working voltage 300/ 500V |
---|---|
Test voltage | 2000V |
Temperature range | Operating temperature range
▸ Fixed laying: -25°C ~ +70°C ▸ Non-stressed temporary mobile laying: -5°C ~ +70°C Short-circuit tolerance limit ▸ Maximum instantaneous temperature: +160°C (duration ≤5 seconds) |
environmental protection | Comply with EU RoHS directive |
Cable parameters
numbering | specification | The finished outer diameter is -ø | Max. Resistance (20° C) | |
---|---|---|---|---|
LS2380205 | 2 x 0.35 mm² | 1.8X3.7 mm | 247.0 ohm/km | Send an inquiry |
LS2380305 | 2 x 0.5 mm² | 2.1X4.2 mm | 39.0 ohm/km | Send an inquiry |
LS2380405 | 2 x 0.75 mm² | 2.3X4.6 mm | 26.0 ohm/km | Send an inquiry |
LS2380505 | 2 x 1.0 mm² | 2.4X4.8 mm | 19.5 ohm/km | Send an inquiry |
LS2380705 | 2 x 1.5 mm² | 2.9X5.8 mm | 13.3 ohm/km | Send an inquiry |
LS2381205 | 2 x 2.5 mm² | 3.3X6.6 mm | 7.98 ohm/km | Send an inquiry |