LiYY-DIN Cca 450/750 V

The cable complies with the requirements of the Construction Products Regulation (EU CPR 305/11) and is designed to limit the generation and spread of fire and smoke.

Multi-core cables for control, signaling, measuring or commanding with very low smoke and toxic gas emissions. It is commonly used in door assemblies, electronic control devices, office equipment, measuring equipment, and anywhere small cable diameters are required. It is lightweight and has excellent flexibility.

Suitable for installation in normal or wet environments for fixed or limited dynamic installations without mechanical stress (not continuous motion).

application

The cable complies with the requirements of the Construction Products Regulation (EU CPR 305/11) and is designed to limit the generation and spread of fire and smoke.

Multi-core cables for control, signaling, measuring or commanding with very low smoke and toxic gas emissions. It is commonly used in door assemblies, electronic control devices, office equipment, measuring equipment, and anywhere small cable diameters are required. It is lightweight and has excellent flexibility.

Suitable for installation in normal or wet environments for fixed or limited dynamic installations without mechanical stress (not continuous motion).

Even if it is protected, it is not allowed to lay underground.

peculiarity

    • IEC 60228
    • IEC 60332-3-24 Class C

    ADDITIONAL INFORMATION

    • Custom core/jacket color

Product structure

conductor Bare copper wire complies with IEC 60228, VDE 0295, class 5 standards
insulation Flame retardant PVC composites (oxygen index ≥30%)
color DIN 47100 compliant (full chromatography)
structure Concentric stranding (HD 21.3 S3 compliant)
Wrap the bag /
shield /
Sheath material: Flame retardant PVC composite (tested by IEC 60332-1)
Sheath color Light grey (RAL 7001 standard colour, ΔE≤3)

Technical parameters

 

Operating voltage Conductor operating voltage

Section≤ 0.75mm²: 300/500V

Section≥ 1.00mm²: 450/750V

Outer sheath working voltage

450/750V (for all sections)

Test voltage Section≤ 0.75mm²: 2000V

Section≥ 1.00mm²: 2500V

Temperature Style Fixed laying conditions: -25°C ~ +70°C

Non-stressed temporary mobile laying: -5°C ~ +70°C

Short-circuit limit temperature

+160°C (maximum duration of 5 seconds, according to IEC 60949)

environmental protection Comply with EU RoHS directive

Cable parameters

numbering specification The finished outer diameter is -ø Max. Resistance (20° C)
LS2380205 2 x 0.35 mm² 1.8X3.7 mm 247.0 ohm/km Send an inquiry
LS2380305 2 x 0.5 mm² 2.1X4.2 mm 39.0 ohm/km Send an inquiry
LS2380405 2 x 0.75 mm² 2.3X4.6 mm 26.0 ohm/km Send an inquiry
LS2380505 2 x 1.0 mm² 2.4X4.8 mm 19.5 ohm/km Send an inquiry
LS2380705 2 x 1.5 mm² 2.9X5.8 mm 13.3 ohm/km Send an inquiry
LS2381205 2 x 2.5 mm² 3.3X6.6 mm 7.98 ohm/km Send an inquiry

Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product. Other sizes and colors are available upon request. The above data is for reference only and is subject to the actual product.

Recently viewed products